Fault 17 Internal processor fault

Subfault: 17.7

Description: Exception error

 

Response: Output stage inhibit

Cause

Measure

Internal computing error (trap) in CPU.

– Switch the device off and on again.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.

Subfault: 17.8

Description: Non-volatile data not loaded

 

Response: Output stage inhibit

System state: Fault acknowledgment with CPU reset

Cause

Measure

CPU was restarted several times without firmware being fully initialized. The non-volatile data is not loaded, the default values remain active.

– Acknowledge fault.

– Check the voltage supply.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.