MOVISUITE® does not create fieldbus interface
Problem
The IEC function blocks for connection to the fieldbus communication are not created.
Remedy
- Check whether the fieldbus connection is activated in the software module and whether the offset is configured.
- The configuration of the fieldbus interface can be viewed in the configuration of the software module in the "Fieldbus interface" configuration menu. The offset (here: start address) must be set to 1 or to the first free address that is intended for the software module. For example, if another software module starts at start address 1 and has 28 process data, the offset of the PES software module must be configured to 29.
- Check whether the fieldbus interface is activated on the MOVI-C® CONTROLLER.
- The fieldbus connection must be activated both in the PES software module and in the MOVI-C® CONTROLLER. The configuration of the fieldbus interface can be viewed in the configuration of the MOVI-C® CONTROLLER in the "Communication" configuration menu in the "Fieldbus" submenu.