Energy storage unit always synchronized (cannot be changed)

 

 

Problem

The Interface_<MDP92A>.ModeDCSync.OUT.xStorageConnected signal in the IEC code is always set to "TRUE".

Remedy
  1. Check that the energy storage unit is configured as separable.
    • The configuration of the energy storage unit can be viewed in the configuration of the software module in the "Energy storage unit" configuration menu in the "Energy storage unit" submenu. "Yes" must be set for "DC connection energy storage unit separable".