PROFINET IO
The parameters "Customer device designation" and "IP settings (IP address, subnet mask and gateway)" are relevant for the PROFINET IO fieldbus option for startup:
- The customer device designation cannot be adjusted using the IEC Editor but can only be set using MOVISUITE®. During startup, the customer device designation is converted into a PROFINET-compliant device name and used to initialize the PROFINET slave stack. This behavior is independent of all reset variants in the IEC Editor. In the IEC Editor, only the PROFINET device name converted after bus startup is displayed on the PROFINET node.
- The IP settings applicable at startup can be set as follows:
- By downloading the application the first time if an application is not yet present on the MOVI‑C® CONTROLLER.
- By changing the IP settings in the project and downloading the project onto the MOVI‑C® CONTROLLER, and performing a cold reset.
INFORMATION
