PROFIBUS
- In order to properly initialize the connection of the PROFIBUS slave to the MOVI‑C® CONTROLLER, the "DP slave address" must be configured before downloading the IEC application. Because the slave address cannot be modified at runtime in the case of the PROFIBUS fieldbus option, a reset (warm, cold, or origin) must be performed to pass a new address to the slave stack.
- The "Baud rate" parameter is a read-only parameter and displays the baud rate negotiated with the master after startup of the bus system.